2
ABB Building Technologies 2/5
1SBC 0101 00 R1001
Setting range A 0.1 … 0.16 1.0 … 1.6 9.0 … 12.5
0.16 … 0.25 1.6 … 2.5 12.5 … 16.0
0.25 … 0.4 2.5 … 4.0 16.0 … 20.0
0.4 … 0.63 4.0 … 6.3 20.0 … 25.0
0.63 … 1.0 6.3 … 9.0
Rated short-circuit
breaking capacity
380 / 400 V I
cu
kA 100 50
Rated service short-circuit
breaking capacity
I
cs
= % I
cu
100 100
Connecting capacity
main circuit
Rigid solid 1 x mm
2
1 … 10
Rigid stranded 1 x mm
2
1 … 10
Flexible without 1 x mm
2
1 … 6
cable end
Auxiliary circuit
Rigid solid 1 x mm
2
0.5 … 2.5
2 x mm
2
0.5 … 2.5
Degree of protection IP 20
Temperature compensation - 25 °C … + 50 °C
Phase failure sensitivity yes
MS 325 Manual Motor Starters
Technical Data